- RBK 00 pro-XT panel installation, top power supply
- RBK 00 pro-X panel installation, bottom power supply
- RBK 00 pro-SG-X 60 mm busbar installation, cable outlet from top, power supply from busbars
- RBK 00 pro-SD-XT 60 mm busbar installation, cable outlet from the bottom, power supply from the busbars
- RBK 1 pro-XT panel installation, top power supply
- RBK 1 pro-X panel installation, bottom power supply
- RBK 1 pro-SG 60-X installation on 60 mm busbars, cable outlet from top, power supply from busbars
- RBK 1 pro-SD 60-XT, 60 mm busbar installation, cable outlet at the bottom, power supply from the busbars
- RBK 1 pro-SG 100-X 100 mm busbar installation, cable outlet from top, power supply from busbars
- RBK 1 pro-SD 100-XT installation on 100 mm busbars, cable outlet at the bottom, power supply via busbars
- RBK 2 pro-XT panel installation, top-mounted power supply
- RBK 2 pro-X panel installation, power supply from below
RBK 2 pro-SG 60-X installation on 60 mm busbars, cable outlet from top, power supply from busbars - RBK 2 pro-SD 60-XT, 60 mm busbar installation, cable outlet at the bottom, power supply from the busbars
- RBK 2 pro-SG 100-X 100 mm busbar installation, cable outlet from top, power supply from busbars
- RBK 2 pro-SD 100-XT, for installation on 100 mm busbars, cable outlet at the bottom, power supply via busbars
| Rated parameters Operating voltage AC - 400–690 V, 40–60 Hz Relay contact rating: 5 A, 250 V ~ NOTE! 1. Fuse links with non-insulated holders
|
- LEDs L1, L2, L3 are lit – device powered by three-phase power supply, all fuse links operational, relay contacts: [21..22] closed; [13..14] open
- LEDs L1, L2, L3 are ‘flashing’ – device with three-phase power supply, fuse links blown, relay contacts: [13..14] – closed; [21..22] – open
- LEDs L1, L2, L3 “do not light up” – no power supply, at least two supply phases missing or fuse links missing, relay contacts: [13..14] – closed; [21..22] – open
|
|