Find out what the RTE switchgears have to offer
The RTE-type outdoor wall-mounted distribution board is designed for the power supply of low-voltage electrical equipment. It is suitable for use, amongst other things, in municipal transformer stations, which are designed to be operated only by authorised personnel.
Suitable for use in TN-S, TN-C, TN-C-S, TT and IT systems
Intended for the power supply of low-voltage electrical equipment
It can be used, for example, in urban transformer stations designed to be operated only by authorised personnel
Options |
Capable of operating in TN-S, TN-C, TN-C-S, TT and IT systems. The RTE type low-voltage (LV) outdoor wall-mounted distribution board can be powered directly or via a main switch disconnector; the following can be used as the main device:
In addition, the RTE LV switchgear may be equipped with:
|
|
| Wall-mounted panel construction made of aluzinc-coated steel sheet, to which busbars are attached using insulators. The power supply busbars are terminated with K4G/3 ball terminals, allowing the connection of cables without cable lugs (1x 50–240 mm² or 3x 50–185 mm²), and are also equipped with ball earthing terminals. Strip-type outgoing units with a 185mm busbar system are mounted directly onto the busbars. |
Operating environmental conditions |
The switchgears aredesigned for operation in a temperate climate and are suitable for installation in the following environmental conditions:
|
Busbar system |
| All busbars and busbar connections are made of copper with a cross-section adapted to the rated currents. The main phase busbars are spaced 185 mm apart, to which terminal blocks are fitted. The protective-neutral PEN busbar for a 4-wire system, with a set of V-type terminals (or screws), is located in the lower part of the switchgears. |