Protection degree IP20 for the application of a fuse link cover
Find out what the PBS 00/100 mm fuse rail has to offer
-
Application
They are designed for installation on busbars as three-phase vertical units, thereby achieving significant space savings in the switchgear compared to classic fuse bases installed on panels. The design takes into account all technical parameters compliant with standards (PN-EN 60269-1, PN-HD 60269-2) and the growing demands of the market.
For installation on a 100 mm busbar system
Can be installed on a 100 mm busbar system with an adapter for its application
Base width 50 mm
Possible cable connection: bridge terminal, M8 screw terminal and V-clamp – cable connection up to 120mm²
Made of thermoplastic polyamide with a halogen-free flame retardant, reinforced with glass fibre
Operating conditions
Environments free from dust, corrosive or explosive gases
Ambient temperature from -25°C to +55°C – when using bases at temperatures between +41°C and +45°C, theIth current value must be reduced by 5%, and in the temperature range from +46°C to +55°C, theIth current value must be reduced by 10%
At altitudes up to 2000 m above sea level
Relative humidity should not exceed 50% at a temperature of +40°C
Outdoors – in enclosures with a protection degree > IP34